Modbus TCP SBOM: what function code 43 provides and where it is missing
Frequently asked questions
With MEI type 14 "Read Device Identification", the basic objects VendorName, ProductCode and MajorMinorRevision (mandatory if FC 43 is implemented), optionally VendorUrl, ProductName, ModelName and UserApplicationName as well as manufacturer-specific objects from 0x80. The standard knows no serial number or hardware revision.
No. FC 43 is a public but voluntary function code; a Modbus server is conformant with any subset of function codes. Many devices answer with exception 01. The service is reliably implemented at Schneider Electric, in many energy meters and in Phoenix and WAGO couplers. Without FC 43, what remains is FC 17 or manufacturer-specific registers.
Through the address list from ARP and switch tables (Bridge MIB) or the engineering project, then a query of each address on TCP 502. Behind gateways, every unit ID has to be queried individually, otherwise the gateway answers with its own identity. The scan should send read codes only and exclude write functions.