In brief · As of November 2026
A B&R plant consists of an X20 CPU or an Automation PC with Automation Runtime, X20/X90 modules on the X2X Link, POWERLINK devices (bus controllers, ACOPOS drives) and Power Panels. From the maintenance PC only CPU, Automation PCs and panels answer via OPC UA and SNMP; the X20 modules on the X2X Link and the POWERLINK devices are not seen by any standard scan. They get into the device list through the controller's System Diagnostics Manager (hardware tree with order number and firmware per module) or from the Automation Studio project. For matching, the Automation Runtime version per controller counts: B&R publishes via the CSAF feed of ABB PSIRT, 29 advisories, 10 new in 2026, without CPE or material number. B&R creates SBOMs and provides them on request via its support team; for the plant you do not need one.
Only CPU, Automation PC and panels answer on the network, X20 modules and POWERLINK devices do not
The controller is an X20 CPU, an Automation PC or a Power Panel with Automation Runtime. Attached are X20 and X90 modules directly on the X2X Link (the local module bus), X20 bus controllers and ACOPOS drives via POWERLINK, plus panels and IPCs via Ethernet. POWERLINK is Ethernet-based but works with a managing node and a fixed cycle; a maintenance PC outside the POWERLINK network does not see the devices.
- Visible via IP from the maintenance PC: CPU, Automation PCs and Power Panels via OPC UA (ServerStatus/BuildInfo, Automation Runtime version) and, depending on configuration, SNMP; switches.
- Only via the controller: all X20/X90 modules on the X2X Link and all POWERLINK devices. The CPU knows their order number and firmware, the network does not.
- Only from the engineering: modules without firmware (simple I/O) and the mapp/APROL software versions, which are to be kept as software.
X20 modules and POWERLINK devices get into the list via the System Diagnostics Manager or Automation Studio
The System Diagnostics Manager (SDM) is the web diagnostics of Automation Runtime: it shows the controller's hardware tree with module type, order number, firmware and hardware revision per X20 module and per POWERLINK device. That is the view of what is running, and the route Werkspilot Scan uses for B&R. The Automation Studio project, by contrast, shows what was planned:
- Automation Studio project (
.apj): hardware configuration with module types and the firmware versions of the X20/X90 modules stored in the project. - System Diagnostics Manager (SDM, web diagnostics in Automation Runtime): hardware and software analysis of the target system with modules and versions – that is the view of what is running.
- Network: POWERLINK participants cannot be reached from the maintenance PC by standard scan; Automation PCs and Power Panels answer via OPC UA (ServerStatus/BuildInfo) and, depending on configuration, SNMP. More in the article on the network scan per control world.
The Automation Studio project names the runtime version and libraries per CPU
For matching, the software per controller matters more than the module list, and it sits in a few files of the Automation Studio project. They are XML and can be read without Automation Studio:
- `Physical/<configuration>/Hardware.hw`: the hardware configuration with CPU, power supply and I/O modules, for each module its type and the version stored in the project.
- `Physical/<configuration>/<CPU>/Cpu.pkg`: the Automation Runtime version of the controller, for example
<AutomationRuntime Version="C4.90" />, plus the mapp packages included. - **
Cpu.sw and Logical/Libraries/…/*.lby**: the software configuration with every library loaded onto the CPU, and per library the description file with its version, for B&R system libraries as well as third-party and in-house libraries.
The project shows the configured state, not necessarily what runs today. What actually runs is shown by the System Diagnostics Manager; a system dump from the SDM records runtime, modules and firmware as a file. At acceptance the two complement each other: the project for libraries and configuration, the dump for the measured versions.
APROL servers are Linux systems with their own package list and time-limited update rights
Many B&R plants are run from a control room server with the APROL process control system. According to B&R, APROL R 4.4 is based on SUSE Linux Enterprise Server 15; R 4.4-00 brought, among others, Linux kernel 5.14, OpenSSL 3.0, MariaDB 10.6 and PostgreSQL 14. The plant SBOM therefore needs the APROL release and the server's package list, which can be exported on the server with built-in tools (rpm -qa).
Security updates for APROL are time-limited. According to the B&R product page, the operating system licences for APROL R 4.4 include SLES subscriptions that ensure ABB security updates via APROL AutoYaST Update for a maximum of two or four years. SLES itself can be used without time limit, but update rights require a valid subscription. An APROL control room without a renewed subscription keeps running and receives no more security updates; the expiry date belongs in the device list for every server.
B&R publishes via the ABB PSIRT CSAF feed, matching runs on the Automation Runtime version
The B&R advisory page offers an "RSS Feed" and a "ROLIE / CSAF feed" – both point to ABB PSIRT, which has carried publication since the acquisition. There is no provider of its own under br-automation.com; seven older CSAF files sit on the B&R page as individual downloads without an index. ABB is listed in the BSI's CSAF aggregator; B&R documents can be recognised by the ID pattern sa<yy>p<nnn>.
| Measurement (7 Oct 2026) | Result |
|---|
| Advisories on the B&R website | 29 (SA22P001 … SA26P012) |
| of which as CSAF in the ABB feed | 14 (all from 15 Jan 2025) |
| Published in 2026 | 10 |
| Published or updated in 2026 (feed) | 14 – all B&R documents were re-released on 14 May 2026 |
| Documents with CPE or PURL (all 74 ABB documents) | 0 |
Example SA25P005 (ANSL server): product tree "Automation Runtime <6.5" and ">=R4.93" – product name plus version range, no material number. Hardware advisories such as SA24P003 (PixieFail, "B&R PCs") name product families. In the numbering SA26P002 to SA26P008 are missing publicly; whether they are under TLP:AMBER or were not published is open.
Because the advisories carry neither CPE nor material numbers, the Automation Runtime version (for example R4.93 or 6.5) per controller is the actual key, supplemented by the device type for hardware and UEFI advisories. The X20 module list is secondary for matching, but belongs in the plant SBOM because firmware advisories for modules can arrive at any time.
With 10 new advisories in 2026, B&R now publishes regularly. Anyone who has not subscribed to the feed misses on average one per month – and the reporting deadline under the CRA runs from awareness, not from publication.
B&R creates SBOMs as part of its development process and, according to its cyber security page, provides them on request via its support team; for the plant you do not need one, the AR version per controller is enough. Every B&R product page also carries a field “CRA (Cyber Resilience Act)”; on 22 Oct 2026 it read “Non-compliant” for the X20CP1584 controller and “In preparation” for the X20CP3687X. This status belongs in the device list for every controller.
For the plant, the Automation Runtime version per controller counts, the module list exists only in the controller
- Record the Automation Runtime version and the device type per B&R controller; that is the column through which 14 of 14 CSAF documents are matched.
- Take the X20/X90 modules from the project or SDM with type and firmware – POWERLINK does not deliver them to an external scan.
- Carry APROL and mapp components as software, not as devices.
Ten new advisories in nine months, and the module list is neither on the network nor in the bill of materials with firmware, but only in the controller. In Werkspilot Scan, B&R is therefore stage 3: the run from the maintenance PC covers CPU, panels and IPCs via OPC UA and SNMP and, after enabling, the X20 and POWERLINK list via the controller's system diagnostics. We are currently trialling this stage with development partners on their plants.
All 13 manufacturers compared: SBOM by manufacturer →
Werkspilot Scan for your own plant: an intro call.
In an intro call we walk through one of your plants: which controllers and fieldbuses are installed, which devices Werkspilot Scan captures from the maintenance PC today, and what comes out as a plant SBOM, every reachable device with manufacturer, order number and firmware version, open items listed individually.
Request an intro call →
Werkspilot keeps these devices per plant and reports when an advisory hits one of them. The figures in this article are our own measurements from 7 Oct 2026; manufacturers change feeds and pages without notice.